Service  /  Critical Power Installation

Single Phase UPSInstallation and Commissioning Australia

Capacity1 to 20kVA
HubsBrisbane / Sydney / Melbourne
Installed from$850 ex GST
CertifiedAS/NZS 3000
Campus server room with network racks and a wall mounted precision cooling unit

Comms rooms / Server rooms / Practices

The size where most Australian businesses actually live. Big enough to matter, small enough that people assume it can be plugged in.

Get an install quote

Direct answer

A single phase UPS runs from a standard 230V supply and covers roughly 1 to 20kVA. Below about 3kVA it is usually plug connected and can be positioned by site staff; above that it is normally hardwired to a dedicated circuit, which makes it licensed electrical work requiring a certificate of compliance under AS/NZS 3000.

Indigi Power and Cooling installs and commissions single phase UPS systems across Australia from $850 ex GST, in comms rooms, server rooms, medical practices, retail back of house and small office floors.

The threshold

Where plug-instops working

Single phase is the size band where the largest number of Australian businesses sit, and it is also where the most corners get cut. A 1kVA tower under a desk genuinely is a plug-in appliance. A 10kVA floor-standing unit feeding a comms room is not, and treating it like one creates a compliance exposure that surfaces at the worst possible moment.

The practical dividing line is the 10A general power outlet. A standard GPO delivers about 2.3kW, so once a UPS needs more than that on its input it cannot be fed from a normal socket. Some units in the 3kVA band use a 15A outlet, which is still plug connected but needs a dedicated 15A circuit installed. Above that, the unit is hardwired.

The second thing that pushes a job over the line is battery runtime. Extending a single phase UPS beyond its internal batteries means an external battery cabinet, and that brings cabling, weight, ventilation and AS 2676 considerations that a plug-in install never has to think about.

Indigi Power and Cooling is Indigenous and Veteran-owned, Supply Nation and ICN Gateway registered. Our installers are licensed electrical workers, and every hardwired install leaves with a compliance certificate and a signed commissioning record.

Which one is your job

Plug connectedor hardwired

Roughly under 3kVA

Plug
connected

  • Feeds from a 10A or 15A outlet
  • Tower or rack mounted, internal batteries
  • Site staff can position and connect it
  • No compliance certificate required
  • Still worth commissioning properly
  • Desks, small comms cabinets, single racks
Roughly 3 to 20kVA

Hardwired

  • Dedicated circuit from the distribution board
  • Licensed electrical worker required
  • Certificate of compliance under AS/NZS 3000
  • Isolation and often a maintenance bypass
  • External battery cabinets where runtime demands it
  • Comms rooms, server rooms, practices, small floors
2.3kW
What a 10A GPO actually delivers
80%
Max recommended load on capacity
12
Typical days including commissioning
35
Years before batteries need replacing

Form factor

Rack, tower or floor standing

The mounting decision is made early and is expensive to reverse, because it drives rack space, floor loading, cable routes and how the unit is serviced.

Table: Single phase UPS mounting options and installation implications
Format Typical capacity Installation considerations
Rack mounted, 2U to 6U 1 to 10kVA Consumes rack units that could hold equipment. Check rail depth and rack weight rating, especially with extended battery modules. Servicing usually means sliding the unit forward, so the rear needs slack
Tower 1 to 3kVA Simplest install. Needs floor space with clearance for ventilation. Suits practices, retail back of house and small comms cabinets
Convertible rack or tower 1 to 10kVA Useful where the room may be racked later. Confirm orientation before install as the display and feet differ
Floor standing 10 to 20kVA Hardwired. Check floor loading and access route including lift capacity and door widths. Needs front and often rear service clearance
External battery cabinet Any, for extended runtime Heavy. Floor loading, ventilation and AS 2676 apply. Cable run between UPS and cabinet must be kept short and correctly rated

Commercial

Single phase installation pricing

Australian rates, ex GST, covering installation and commissioning. Equipment is quoted separately.

Up to 3kVA
$850
Ex GST / from

Positioning, connection, commissioning and handover. Often plug connected at this size, so frequently a same-day job.

3 to 10kVA
$1,250
Ex GST / from

Hardwired to a dedicated circuit with isolation provided, commissioned and certified under AS/NZS 3000. The most common single phase install we do.

10 to 20kVA
$1,800
Ex GST / from

Hardwired with external battery cabinet and maintenance bypass where specified. Access and floor loading checked at inspection.

Add-ons priced at quote: new dedicated circuit where none exists, maintenance bypass switch, external battery cabinet, network management card and monitoring setup, out of hours work, and removal and disposal of an existing unit.

Scope

What the install includes

Load assessment and sizing check

We measure the actual load rather than adding nameplate ratings, which routinely produces a smaller and cheaper UPS than a paper calculation. We also check headroom, because a UPS should sit around 80 per cent of capacity at most to hold its rated runtime.

Supply and circuit work

Confirming the board has a spare way and adequate capacity, installing a dedicated circuit where the unit is hardwired, and providing isolation so the UPS can be worked on without dropping the room.

Physical installation

Racking or positioning the unit with correct service clearances, installing any external battery cabinet, cable termination, earthing and labelling. Old unit removed and disposed of if we are replacing one.

Commissioning and transfer testing

Battery string voltage, polarity and torque checks, transfer testing on line to battery and back, load testing at the real load, and runtime verification so you know what you actually have rather than what the brochure claims.

Monitoring and handover

Network management card configured, alarms and shutdown software set up where required, compliance certificate and commissioning record issued, and a maintenance schedule handed over with the site.

Where they go

Rooms we install into

Questions

Single phaseinstall FAQs

What people ask before booking a single phase install. If yours is not here, call 1800 046 344.

What is a single phase UPS?

A single phase UPS runs from a standard 230V single phase supply, the same supply that feeds general power outlets in most Australian buildings. Capacities run from around 500VA up to about 20kVA. Above that, and in any building with a three phase supply feeding a significant load, a three phase UPS is normally used instead. Single phase units cover comms rooms, small server rooms, medical practices, retail back of house and small office floors.

Can I install a single phase UPS myself?

Only if it is plug connected. A UPS that feeds from a standard 10A or 15A outlet can be positioned and plugged in by site staff, though it should still be commissioned and load tested properly. Once a unit is hardwired into the distribution board, which is typical above about 3kVA, it becomes fixed electrical wiring and must be installed by a licensed electrical worker and certified under AS/NZS 3000.

How much does single phase UPS installation cost?

Indigi Power and Cooling installs single phase UPS systems from $850 ex GST up to 3kVA, from $1,250 for 3 to 10kVA and from $1,800 for 10 to 20kVA. Those figures cover installation and commissioning; the equipment is quoted separately. Adding a new dedicated circuit, a maintenance bypass switch, an external battery cabinet or out of hours work is priced at quote.

What size single phase UPS do I need?

Size to the measured load, not the nameplate ratings, and leave headroom. A UPS running at more than about 80 per cent of its capacity loses runtime quickly and has no room for growth. As a rough guide, a small comms room with a couple of switches and a firewall usually sits under 1kVA, a single well-populated rack around 3 to 5kVA, and a small server room 6 to 15kVA. We measure at site inspection rather than estimating.

Should the UPS be rack mounted or floor standing?

Rack mounting keeps everything in one cabinet and is tidy, but it consumes rack units you might want for equipment, and extended battery modules consume more. Check the rack weight rating before committing. Tower and floor standing units free up rack space and are easier to service, but need floor area with ventilation clearance. Above about 10kVA the decision is usually made for you, since the unit is floor standing.

How long will the batteries last?

Three to five years for standard sealed lead acid batteries in a temperature-controlled room, shorter where ambient temperature is high. Battery life is the single biggest factor in whether a UPS performs during an outage, which is why we hand over with a maintenance schedule and recommend runtime verification at least annually rather than trusting the front panel.

Can you replace an existing UPS without downtime?

In most cases yes. Where a maintenance bypass exists we transfer the load onto it and swap the unit live. Where there is none, we can install a temporary bypass or schedule the brief interruption out of hours. Retrofitting into a room with no bypass provision is the situation worth raising at site inspection, because it changes both the method and the price.

Equipment

Single phasebrands we install

We install what we stock and service, so the technician who commissions your unit is the one who will maintain it. Equipment bought elsewhere is no problem: we will quote the installation on its own.

Eaton
9PX 1 to 11kVA9SX and 9SX AP5PX and 5SCRack, tower and convertible
View range
Schneider APC
Smart-UPSSmart-UPS On-LineSmart-UPS UltraExternal battery packs
View range
Vertiv Liebert
GXT5 double conversionGXT5 lithium ionITA2 5 to 40kVA
View range
PowerShield
Centurion and Centurion ProDefender seriesAustralian designed and supported
View range
Batteries
Eaton SLACSB and Vision AGMPower SonicExternal battery cabinets
View range
Accessories
Maintenance bypass switchesNetwork management cardsRack PDU
View range

Replacing an ageing unit? We remove and dispose of the old UPS and its batteries responsibly as part of the install. Tell us the make, model and capacity and we will quote the swap, including whether it can be done without dropping the load.

Partner with Us

Reliable Power & Cooling Solutions from Indigi Power & Cooling
Expert supply, installation, and contracting services for critical infrastructure across Australia.

Request a Quote