Evikon E2638-HFC Refrigerant Detector
HFC and HFO Refrigerant Leak Detection for Data Centres, CRAC Cooling Systems and Refrigeration Plants
The Evikon E2638-HFC is a fixed refrigerant detector-transmitter designed for continuous monitoring of HFC and HFO refrigerant leaks in commercial and industrial environments. Part of the Evikon PluraSens family, it uses a stable long-life metal-oxide semiconductor sensor sensitive to a wide range of refrigerant compounds, with detection resolution down to 1 ppm and ranges to 2,500 ppm.
In data centres and server rooms, CRAC precision cooling units operate on refrigerant-based circuits. A refrigerant leak in an enclosed space can displace oxygen and create hypoxic conditions for personnel without any visible warning. The E2638-HFC provides continuous monitoring with configurable alarm thresholds, relay outputs for ventilation or alarm control, and RS485 Modbus RTU integration with BMS and fire safety systems.
Supplied by Indigi Power & Cooling across Australia.
Applications
-
Data centres and server rooms (CRAC and CRAH refrigerant circuit monitoring)
-
Precision cooling plant rooms
-
Cold storage warehouses and refrigeration plants
-
Skating arenas and large-scale refrigeration facilities
-
Hotels and commercial HVAC plant rooms
-
Any enclosed environment with refrigerant-based cooling equipment
Refrigerants Detected
The E2638-HFC sensor is sensitive to a wide range of HFC and HFO compounds including:
R-32, R-134a, R-404a, R-407c, R-410a, R-449a, R-454a, R-454b, R-454c, R-507, R-513a, R-514a, R-1234ze, and other halocarbon gases.
For applications requiring detection of a specific refrigerant to precise ppm accuracy, an optical NDIR sensor variant is available on request.
Technical Specifications
| Parameter | Detail |
|---|---|
| Model | E2638-HFC |
| Product Family | PluraSens (Evikon MCI) |
| Gases Detected | HFC and HFO refrigerants — R-32, R-134a, R-404a, R-407c, R-410a, R-449a, R-454a, R-454b, R-454c, R-507, R-513a, R-514a, R-1234ze and others |
| Sensor Technology | Metal-oxide semiconductor (standard); Optical NDIR available on request |
| Sampling Method | Diffusion |
| Detection Range | 0 to 1,000 ppm or 0 to 2,500 ppm halocarbon gas |
| Resolution | 1 ppm |
| Minimum Alarm Setpoint | 250 ppm |
| Alarm Setpoints | Two user-settable alarm thresholds |
| Sensor Lifetime | Greater than 5 years |
| Power Supply | 12 to 36 VDC (default); 24 VAC or 230 VAC options available |
| Digital Interface | RS485 Modbus RTU |
| Analog Outputs | 2 x 4-20 mA or 0-10 V, user settable |
| Relay Outputs (option) | 2 x SPST relays (closing contact), rated 250 VAC / 30 VDC, 5 A max |
| Enclosure Material | Grey ABS plastic |
| Mounting | Wall mount |
| IP Rating | IP65 |
| Dimensions | H90 x W145 x D55 mm |
| Operating Temperature | -30 to +60 degrees C |
| Operating Humidity | Below 95 %RH |
| Certifications | CE |
Key Features
-
Stable long-life metal-oxide semiconductor sensor with greater than 5 year service life
-
Sensitive to a wide range of HFC and HFO refrigerant compounds on a single unit
-
Resolution of 1 ppm for precise early leak detection
-
Two user-settable alarm setpoints for staged alarm and ventilation response
-
Optional relay outputs for direct connection to ventilation fans, alarms, or fire panels
-
Dual analog outputs (4-20 mA or 0-10 V) and RS485 Modbus RTU for BMS integration
-
IP65 rated wall-mount enclosure for plant room and industrial environments
-
NDIR optical sensor variant available on request for gas-specific precision measurement
-
Power supply options from 12 VDC through to 230 VAC to suit existing infrastructure
Documents
Supply and Installation by Indigi Power & Cooling
Indigi Power & Cooling supplies Evikon MCI gas detection equipment and provides installation, commissioning, and BMS integration services for data centres, precision cooling environments, and commercial refrigeration plant rooms across Queensland, New South Wales, Victoria, and Papua New Guinea.
The E2638-HFC is installed as part of a complete refrigerant safety solution including sensor placement design relative to CRAC unit locations and air movement paths, relay wiring to ventilation or fire panels, and analog or RS485 integration to your building management system.