UQD Quick Disconnect Coupling, Male ORB ISO 11926-3

UQD Quick Disconnect Coupling, Male ORB ISO 11926-3

This is a flat-face, push-to-connect stainless steel quick disconnect coupling for data centre liquid cooling loops, in the Open Compute Project UQD sizes UQD02, UQD04 and UQD06, with a male O-ring boss thread to ISO 11926-3. Manufactured by Alfagomma and supplied by Indigi Power and Cooling, who buy direct. EPDM seals matched to the coolant hose, stainless steel body, and every unit helium leak tested rather than batch sampled.

Couplings with an O-ring boss thread in the UNF series. Common on North American hardware and on most coolant distribution units sold into Australia, including the Vertiv range.

Part numbers and dimensions

Table: UQD Quick Disconnect Coupling, Male ORB ISO 11926-3, part numbers and dimensions by UQD size.
UQD size Part number Thread E F G H J Hex
UQD02 HZ213010-040400 7/16-20 UNF 17.3 mm 29.3 mm 9.1 mm 13.5 mm 6.6 mm 14.0 mm
UQD04 HZ213010-060600 9/16-18 UNF 19.6 mm 38.2 mm 11.1 mm 10.6 mm 11.1 mm 17.0 mm
UQD06 HZ213010-080800 3/4-16 UNF 24.6 mm 41.8 mm 11.0 mm 11.0 mm 14.3 mm 22.0 mm

Thread sizes are 7/16-20 UNF for UQD02, 9/16-18 UNF for UQD04 and 3/4-16 UNF for UQD06. O-ring boss ports seal on the face rather than the thread, so O-ring condition matters more than thread torque.

Why these details matter

Flat face matters for two reasons: very little coolant is lost on disconnect, and no air is drawn in on reconnection. Air in a technology cooling loop causes pump cavitation, hot spots inside cold plates and corrosion. It is also simply easier to wipe clean before mating, which keeps particulate out.

Helium leak testing finds leak paths that water will not move through fast enough to register on a pressure decay test. On a loop at 20 bar through hundreds of connection points, the leak that only appears after six months in service is exactly the one worth catching at the factory. Every unit is tested, not a batch sample.

EPDM seals are matched to the EPDM coolant hose tube and to propylene glycol coolants. Do not mix seal materials across one loop.

Specifying across a site

Keep one coupling family and one seal material across the whole site. Mixed coupling families on a single row is the most common liquid cooling problem we are called to, and it cannot be fixed without replacing hardware. The binding coolant chemistry specification normally comes from your server or cold plate vendor rather than the CDU vendor, and operating outside it can void hardware warranty.

Frequently asked questions

What does UQD mean, and will these mate with another manufacturer?

UQD stands for universal quick disconnect. The sizing and dimensional envelope come from the Open Compute Project specification, which is why several manufacturers all offer UQD02, UQD04 and UQD06 that interchange dimensionally. They will physically mate. They do not necessarily perform identically, because flow coefficient, seal material and spill volume still vary, so standardise on one family across a site and record the part numbers.

Which size should I use?

Size to the flow the node actually needs, then match the hose to the coupling rather than the other way round. As a guide, UQD02 suits lower flow nodes, instrumentation branches and bleed lines; UQD04 is the common size for single-socket and mid-range direct-to-chip nodes; UQD06 suits high flow and multi-socket accelerated servers.

Can these be disconnected while the loop is running?

Flat-face quick disconnects are designed to be connected and disconnected in service with minimal spill, which is what allows a rack to be worked on without draining the loop. Follow your own isolation procedure and the server vendor instructions. Where a genuinely zero-spill disconnect is required we can quote dry-break couplings instead.

Why is there no price shown?

Quantity and configuration change the number, and these are normally quoted as part of an assembly list rather than bought singly. Send a rack elevation or a parts list and we will price it.

Related

Quoted against your rack elevation

Send the rack layout, the cold plate port types and the flow per node and we will come back with sizes, assembly lengths, part numbers and an installed price. Indigi Power and Cooling buys these components direct, and is Indigenous and Veteran owned, Supply Nation and ICN Gateway registered.