Vertiv™ Liebert® ITA2 | ITA-30kVA-3 PHASE | Indigi Power & Cooling
Vertiv™ Liebert® ITA2 | ITA-30kVA-3 PHASE | Indigi Power & Cooling
The Vertiv Liebert ITA2 30kVA is a rack or tower online double-conversion UPS delivering 30 kW at unity (1.0) power factor with three-phase power, protecting critical loads across Australia. It runs true VFI double conversion with up to 95% efficiency, or up to 99% in ECO mode, and is supplied, installed and maintained by Indigi Power and Cooling, an Indigenous and Veteran-owned specialist.
The Vertiv Liebert ITA2 is a fully digital, online double-conversion UPS built for data centres and larger critical three-phase loads. The 30 kVA model combines a compact rack-tower chassis with unity output power factor and best-in-class efficiency, giving you clean, continuous power with low running costs. It is part of the ITA2 5kVA to 40kVA family, all sharing the same control platform, communications and battery approach.
At 30 kVA it steps up to data centre and industrial duty, delivering three-phase power with the headroom to protect dense racks, cooling controls and critical plant from a single, space-efficient cabinet.
Why the ITA2 30kVA leads
Unity power factor
Delivers the full 30 kW of real power at unity power factor, so every kVA is usable watts for modern IT loads.
Up to 95% efficient
True double-conversion efficiency up to 95%, and up to 99% in ECO mode, cutting running costs and heat.
Rack or tower
A 3U rack or tower chassis that installs either way, so it fits a rack row or stands alone in a comms room.
Wide input window
A wide input voltage and frequency range (50/60 Hz (range 40 to 70 Hz)) rides through unstable mains and generator supply, sparing the battery.
Fast battery recharge
A powerful charger (13 A) restores runtime quickly after an outage, so the UPS is ready for the next event.
Smart, quiet cooling
Intelligent variable-speed fans keep noise to around 60 dBA and save energy at partial load.
Liebert ITA2 in action
Watch Vertiv's overview of the Liebert ITA2 platform, covering its rack-tower flexibility, efficiency and channel-ready design.
True online double-conversion protection
The ITA2 30kVA is a VFI-SS-111 online double-conversion UPS, which means incoming mains is rectified to DC and rebuilt into a clean sine wave by the inverter, and your load always runs from that inverter. There is no transfer time when the mains fails, and mains-borne problems such as sags, spikes, frequency drift and harmonics never reach your equipment. For data centres and larger critical three-phase loads, that is the difference between conditioned, uninterrupted power and a UPS that only reacts once a problem has already passed through.
Efficiency and running costs
Running cost matters over the life of a UPS. The 30 kVA reaches up to 95% efficiency in full online double-conversion mode, so very little of your energy is lost as heat, which also reduces the cooling load in the room. Where the supply is stable enough, ECO mode lifts efficiency to up to 99% for further savings. Intelligent variable-speed fans add to this by running only as fast as the load and temperature require, keeping noise to around 60 dBA and cutting energy use at partial load.
Technical specifications
| Specification | Detail |
|---|---|
| Model / part number | ITA-30k00AL3302P00 |
| Topology | online double conversion (VFI-SS-111) |
| Capacity | 30 kVA / 30 kW at unity (1.0) power factor |
| Input | 380/400/415 V three-phase (4-wire) |
| Input voltage range | three-phase, wide input window |
| Input frequency | 50/60 Hz (range 40 to 70 Hz) |
| Input power factor | 0.99 |
| Input current THD | less than 3% |
| Output | 380/400/415 V three-phase |
| Output voltage THD | less than 2% (linear load) |
| Overload capacity | 105 to 125% for 5 min, 125 to 150% for 1 min, 150% for 200 ms |
| Double-conversion efficiency | up to 95% |
| ECO mode efficiency | up to 99% |
| Battery blocks per string | 30, 32, 34, 36, 38 or 40 (12 V blocks) |
| Battery charger | 13 A |
| Dimensions (W x D x H) | 430 x 570 x 130 mm (3U rack or tower) |
| Net weight | approximately 24 kg |
| Noise at 1 m | around 60 dBA |
| Operating temperature | 0 to 50 degrees C |
| Maximum altitude | up to 3000 m |
| Standards | IEC/EN 62040-1 (safety), IEC/EN 62040-2 (EMC), VFI-SS-111 (IEC 62040-3) |
Battery runtime and extended backup
The 30 kVA supports external battery cabinets so runtime can be scaled to the autonomy your site needs, from a few minutes of ride-through for a generator handover to extended backup for longer outages. Battery strings can be arranged flexibly between the number of blocks per string and paralleled units, which helps you reuse existing battery systems and control the up-front battery investment. For a runtime figure matched to your exact load and battery configuration, use our UPS runtime and battery calculator or ask Indigi to size it for you.
For a unit of this size we usually recommend a maintenance bypass so the UPS can be isolated and serviced without dropping the load, and a preventative maintenance plan that includes battery capacity testing. Indigi can supply the 30 kVA as a complete package with external batteries, bypass and a service agreement, engineered and commissioned to AS/NZS 3000.
Communications and monitoring
The 30 kVA integrates with your monitoring and building management systems out of the box. It provides voltage-free (dry) contact ports, a USB interface and a Vertiv IntelliSlot bay for an SNMP, Modbus or relay card, plus an integrated network port with HTTP access for browser-based monitoring. That lets your team see UPS status, load and battery health remotely and trigger a graceful server shutdown before the battery is exhausted.
Battery management and extended runtime
A wide input voltage window lets the 30 kVA keep drawing from the mains or a generator across a broad range before it calls on the battery, which reduces cycling and prolongs battery life. When backup is needed, a powerful charger (13 A) restores the string quickly after an outage. Automatic and manual self-tests flag a weak battery early, and temperature-compensated charging protects battery life in warm rooms. Runtime scales with battery modules or external cabinets, so the same UPS can cover a brief generator handover or a longer ride-through.
How the ITA2 30kVA compares
| Feature | Liebert ITA2 30kVA | Typical rack online UPS |
|---|---|---|
| Topology | Online double conversion (VFI-SS-111) | Often line-interactive at this size |
| Output power factor | unity (1.0) | Commonly 0.8 to 0.9 |
| Peak efficiency | up to 95% (up to 99% ECO) | Typically 92 to 95% |
| Form factor | Rack or tower, 430 x 570 x 130 mm | Usually rack-only or tower-only |
Sizing the ITA2 30kVA for your site
For three-phase loads up to 30 kW, the 30 kVA protects a dense rack or a room of plant from one cabinet. Pair it with external battery cabinets sized to your required autonomy, and consider a maintenance bypass so the UPS can be serviced without dropping the load.
Applications
The Liebert ITA2 30kVA suits data centres and larger critical three-phase loads. Indigi deploys it across:
- Server rooms and comms rooms needing clean, protected power
- Data centre and edge racks where space and efficiency matter
- Healthcare and cold-chain and other loads that cannot lose power
- Industrial control, automation and telecom cabinets
Installation and maintenance
Indigi Power and Cooling supplies the Liebert ITA2 30kVA with genuine Vertiv batteries and accessories, and provides three-phase installation and commissioning to AS/NZS 3000, plus preventative maintenance and battery replacement. See our three-phase UPS installation and commissioning and UPS maintenance services.
Frequently asked questions
Is the Vertiv Liebert ITA2 30kVA a true online UPS?
Yes. It is a true online double-conversion UPS classified VFI-SS-111, so the load always runs from the inverter with zero transfer time and full conditioning, not just battery backup during an outage.
What power factor and real power does the 30kVA deliver?
It delivers 30 kW at unity (1.0) power factor, so the full kVA rating is usable watts for modern IT loads.
Can the ITA2 30kVA be rack or tower mounted?
Yes. The 430 x 570 x 130 mm (3U rack or tower) chassis mounts in a standard rack or stands as a tower, so it fits a rack row or a floor position in a comms room.
How long will it run on battery?
Runtime depends on load and the number of battery modules or external cabinets fitted. Use our UPS runtime and battery calculator, or ask Indigi to size it for your load.
Do I need an electrician to install it?
A three-phase UPS of this size should be installed and commissioned by a licensed electrician under AS/NZS 3000. Indigi provides installation, commissioning and ongoing maintenance across Australia.
Does Indigi service the Liebert ITA2 across Australia?
Yes. Indigi supplies, installs and maintains the ITA2 range from hubs in Brisbane, Sydney and Melbourne, with national coverage including genuine Vertiv parts and battery replacement.
Related products and services
- Full Vertiv Liebert ITA2 5kVA to 40kVA range
- All Vertiv Liebert UPS systems
- Vertiv UPS accessories and batteries
- UPS maintenance plans
- UPS runtime and battery calculator
|
Get a price on the Liebert ITA2 30kVA Tell us your load, runtime target and site, and we will quote the right ITA2 configuration with installation and maintenance. Indigi Power and Cooling is an Indigenous and Veteran-owned specialist, Supply Nation and ICN Gateway registered. Contact Indigi Power and Cooling |

Partner with Us
Reliable Power & Cooling Solutions from Indigi Power & Cooling Expert supply, installation, and contracting services for critical infrastructure across Australia.